QEED QE-CURRENT-485: CONVERTISSEUR UNIVERSEL DE COURANT / TENSION Analyseur de courant / tension AC / DC
Livraison:
QEED QE-CURRENT-485: CONVERTISSEUR UNIVERSEL DE COURANT / TENSION
Analyseur de courant / tension AC / DC
Le QE-CURRENT-485 est le premier CONVERTISSEUR ET ANALYSEUR DE COURANT/TENSION TOUT EN UN -
du marché. Il vous permet de connecter toutes sortes de transformateurs/ Capteurs de courant.
Il peut mesurer en même temps une sonde température (PT100 ou NTC).
Montage sur rail DIN, adapté pour tous les panneaux électriques.
L’appareil est équipé d’une sortie analogique configurable, une sortie numérique et le
RS485 Modbus RTU.
Logiciel de configuration gratuit.
Related Products
INPUT - CURRENT SENSOR
One of:
● ROGOWSKI probes.
● Current transformer with secondary 1A / 5A.
● Current / Voltage transformer with secondary ±10 Vpk or ± 1 Vpk.
● Current transformer with secondary 333 mV.
● Current transducer with secondary 100 mA AC / DC.
● HALL sensor, with his power supply (+/-15 Vdc).
INPUT - TEMPERATURE
● PT100 2-3 wires or NTC (10 k/ 100 kohm / custom) not isolated.
IMPORTANT NOTE:
● IT REQUIRES ISOLATED PRIMARY
CURRENT / VOLTAGE SENSOR;
● DURATION OF FLASH FOR DATA STORAGE:
3,5 YEARS.
AVAILABLE VERSION
QE-CURRENT-485: Current / Voltage converter, Analog Output and
RS485 Modbus serial; Measures RMS, AC and DC , average
minimum and maximum measurements, frequency and Crest Factor.
The temperature or the resistance measurement.
QE-CURRENT-485-H: Current / Voltage converter and ANALYZER,
analog and serial output RS485 Modbus. With all the measurements
of the basic version and harmonic analysis up to the 63rd, THD, I
peak and measurement of internal temperature of the module (to
understand the temperature of the panel).
POWER SUPPLY 10…30 Vdc, Protection
against reverse polarity and over-temperature
ABSORPTION 2,5 VA max
PROTECTION INDEX IP 20
AVAILABLE MEASUREMENTS
Irms Irms MAX Irms min Irms mean
Ah of Irms
Idc Idc MAX Idc min Idc mean
Ah of Idc
Iac Iac MAX Iac min Iac mean
Ah of Iac
Frequency Crestfactor
I peak * THD *
Temperature (PT100 / NTC) Internal Temp *Resistance
Of PT100/NTCprobe
Harmonic analysis up to the 63rd harmonic *
The measurements into the table are the same for
the VOLTAGE.
Available on version QE-CURRENT-485-H
SAMPLING RATE 6400 Hz @ 50 Hz
ACCURACY OF ANALOG OUTPUT < 0,1% F.S.
BAUD RATE 1200...115200 Baud (standard 9600)
TEMPERATURE COEFFICIENT < 100 ppm/°C
WORKING TEMPERATURE -10°C... +60°C
STORAGE TEMPERATURE -40°C... +85°C
HUMIDITY 10...90% not condensing
ALTITUDE Up to 2000 m s.l.m.
MOUNTING Din rail mounting, designed for
mounting on bus (connector not included)
CONNECTIONS n°2 removable terminals 10 pole
- 3,5 mm
CE STANDARDS EN61000-6-3; EN61000-4-2;
EN61000-4-3; EN61000-4-4; EN61000-4-5 ; EN61000-
4-6; EN61010-1
DIMENSIONS 93 x 17,7 x 68,3 mm
(terminal excluded)
WEIGHT 55 g
PLASTIC CASE PBT, grey
DIP-SWITCH 2 pole (Baudrate and address)
LED N°5: Power (Green), Comm (Yellow), TX e RX
(Red), Dout (Green)
CONFIGURATION With software FACILE
QE-CURRENT-485 or via RS485 Modbus.
Comunication to free interface program for:
- configuration of all the available parameters;
- possibility of firmware upgrade (if available).
ACCURACY QE-CURRENT-485
20/100 mA CHANNEL
CREST FACTOR: 4 (RELATIVE OF 100 mA)
RANGE: 1 mA < I < 5 mA MAX ERROR: 1 %
RANGE: 5 mA < I < 100 mA MAX ERROR: 0,5 %
TEMPERATURE COEFFICIENT: < 100 ppm/°C
BANDWIDTH (-3dB) > 2 KHz
±1 Vpk CHANNEL
RANGE: 10 mV < V < 50 mV MAX ERROR: 1 %
RANGE: 50 mV < V < 1 V MAX ERROR: 0,5 %
TEMPERATURE COEFFICIENT: < 100 ppm/°C
BANDWIDTH (-3dB) > 2 KHz
±10 Vpk CHANNEL
RANGE: 100 mV < V < 500 mV MAX ERROR: 1 %
RANGE: 500 mV < V < 10 V MAX ERROR: 0,5 %
TEMPERATURE COEFFICIENT: < 100 ppm/°C
BANDWIDTH (-3dB) > 800 Hz
CHANNEL OF TEMPERATURE
0CHANNEL
RANGE: -200 °C .. +600 °C
ERROR: ± 1.2 °C on reading
T E M P E R A T U R E
COEFFICIENT:
< 100 ppm/°C
NTC
CHANNEL
RANGE: 200 Ω .. 20 KΩ 20 KΩ .. 300 KΩ
ERROR: ± 1.2 °C on reading ± 1.6 °C on reading
T E M P E R A T U R E
COEFFICIENT:
< 100 ppm/°C
2 03 2016
CONDITION OF TEST: sinusoidal input 50-60 Hz, integrator disabled, temperature 25 °C.