QEED QI-HSC-50 SPLIT CORE HALL EFFECT CURRENT TRANSFORMER
Delivery:
The QI-HSC sensor allows the measurement of continuous and alternating currents with excellent precision and a wide measuring range.
The QI-HSC, which is openable, allows you to implement without disconnecting the conductors.
Removable screw terminals are very easy to install.
The HSC sensors are used in all measurement requirements of continuous currents and with variable frequency (up to 20 kHz), in battery control systems such as UPS, safety power supplies and energy storage), power electronics. The output signals can be connected to a special instrumentation, PLC, etc.
Related Products
QEED QI-HSC-50 SPLIT CORE HALL EFFECT CURRENT TRANSFORMER
Technical features :
NOMINAL CURRENT MEASUREMENT: 50 A AC/DC 100 A AC/DC
AUXILIARY POWER SUPPLY :± 12 … 15 Vdc
WORKING FREQUENCY: From DC up to 20 kHz
LOAD RESISTANCE: min 10 kohm
ABSORPTION: @ 15 V dc 25 mA
VOLTAGE OUTPUT: @ Nominal current Ip = 0 ± 25 mV
VOLTAGE OUTPUT: @ Nominal current Ipn ± 4 V ±1%
ACCURACY: ± 1%
LINEARITY :< 1%
THERMAL DRIFT: ± 1 mV / °C
RESPONSE TIME: 0...90% 10 μs
ISOLATION PRIMARY/SECONDARY: 3 kV
WORKING TEMPERATURE: -25 °C...85 °C
STORAGE TEMPERATURE: -40 °C...100 °C
CONNECTION: Removable Connector for cable section 0,2 ÷ 2,5 mm²
WEIGHT: 80 g
ORDER CODE QI-HSC-50
Hole window : Ø21mm
Primary Current: 50A
Output: +- 4 V