QEED QE-POWER-T-PLUS THREE PHASE NETWORK ANALYZER
Delivery:
THREE PHASE NETWORK ANALYZER - 17,5 mm
Compliant to POWER QUALITY REQUIREMENT
ALL-IN ONE Current Transformers Input
The smallest three phase network analyzer for all current probes.
Ready to be connected with your Monitoring/Datalogger system.
RS485 Modbus RTU and configurable digital contact available.
All in one Current Transformers input and three versions to cover all your needs
Three versions: QE-POWER-T-STD , QE-POWER-T-PLUS, QE-POWER-T-PRO
Related Products
QEED QE-POWER-T-PRO THREE PHASE NETWORK ANALYZER
POWER SUPPLY: 10...40 V DC o 19...28 V AC - 50/60Hz
VOLTAGE INPUT: Direct connection up to 500V RMS maximum (40...70Hz)
Transform Ratio: for CT and VT available
OUTPUT: RS485 Mobus RTU and
Digital Contact: (<40 V, <100mA)
AVAILABLE MEASURE
I rms, V rms
I pk, V pk per phase
P, P1, P2, P3 : Active Power ( W )
Q, Q1, Q2, Q3 : Reactive Power (VAR)
S, S1, S2, S3 : Apparent Power (VA)
Frequency
Power Factor total and per phase (Inductive / Capacitive)
Energy ( kWh) total and per phase
Bidirectional Energy (kWh), positive and negative per phase and total
Active and Reactive Energy (kVARh) - ( Inductive / Capacitive ) total and per phase
Crest Factor total and per phase
Tanφ, per phase and average (inductive/Capacitive)
Power Factor average, total and per phase
Power Factor Distortion (inductive/Capacitive) per phase/avg
- THD (V, I )
Power measurement : min, average and max per phase and total
- Monitoring phase sequence
Max Demand over 15minutes, total and per phase
Time at which arises max demand (per month), total and per phase
Time above a threshold, total and per phase
K Factor ( IEEE Standard 1100-1992)
Accuracy ( @25°C, 50Hz) QE-POWER-T
VOLTAGE (Un: 230/400 V) +/- 0,5% RDG ( 10...100% Un )
CURRENT (In= 5A) +/- 0,5% RDG ( 5...100% In )
FREQUENCY +/- 0,1 Hz from 40...70Hz;
POWER ACTIVE : +/- 0,5% RDG ; REACTIVE : +/- 0,5% RDG
ENERGY ACTIVE: Class C according to EN50470-1/3 or Class 0,5 S according to EN62053-22
REACTIVE: Class 0,5 S according to EN62053-24
Other features:
ABSORPTION < 500mW @ 24V DC
SAMPLING RATE 6400 Hz @ 50Hz
BAUDRATE RS485 from 1200...115200 Baud (standard 9600 )
THERMAL DRIFT < 100ppm/°C
WORKING TEMPERATURE -10°C...+60°C
STOCK TEMPERATURE -20°C...+85°C
RELATIVE HUMIDITY 10... 90% not condensing
ALTITUDE Up to 2000 m s.l.
FIXING SYSTEM On DIN rail , ready to be mounted on T-BUS system
CONNECTIONS n°4 removable connectors: 2, 3, 6 poles 3,5mm step, 4 poles 5,08mm step
DIMENSIONS 93 x 17,5 x 68,3 mm (without connectors )
WEIGHT 60 gr.
DIP-SWITCH 2 poles ( Baudrate and Address) for connection with the configuration software FACILE
LED N°5 : Power (Green), Comm (Yellow), TX e RX (Red), Digital contact (Green)
STANDARD REFERENCES EN61000-6-2; EN61000-6-4; EN61000-4-2; EN61000-4-3; EN61000-4-4; EN61000-4-5;
EN61000-4-6; EN61010-1; EN61010-2-30
- chevron_left
- 1
- chevron_right
Your review appreciation cannot be sent
Report comment
Report sent
Your report cannot be sent
Write your review
Review sent
Your review cannot be sent